Energy
efficient as well as space saving, R2F panels are both
radiant and convective. These panels provide more
comfort at a lower room temperature than convective
heaters. Various average water temperatures (AWT) are
shown here for convenience, but for more specific
conditions use the appropriate correction factor with
the 215°F rating. Please see the technical pages for
the correction factor best suited to the design
conditions. |
BTUH/ft Ratings @ 65°F EAT |
| MODEL |
HEIGHT inches |
DEPTH inches |
215°F |
180°F |
140°F |
R2F-1 |
2.8 |
4.8* |
980 |
689 |
395 |
R2F-2 |
5.7 |
4.8* |
1590 |
1118 |
640 |
R2F-3 |
8.6 |
4.8* |
2020 |
1421 |
813 |
R2F-4 |
11.5 |
4.8* |
2420 |
1701 |
974 |
R2F-5 |
14.4 |
4.8* |
3100 |
2177 |
1246 |
R2F-6 |
17.3 |
4.8* |
3470 |
2443 |
1398 |
R2F-7 |
20.3 |
4.8* |
3846 |
2707 |
1549 |
R2F-8 |
23.1 |
4.8* |
42112 |
2963 |
1696 |
R2F-9 |
26.1 |
4.8* |
4432 |
3119 |
1785 |
R2F-10 |
29 |
4.8* |
4644 |
3269 |
1871 |
* 3.4" depth for pedestal mount radiators |