Model Type RS2
BTUH/ft Ratings

MODEL
TYPE |
HEIGHT
H |
BTUH/FT OUTPUT
@ LISTED AWT & 65°F EAT |
DRY WT
lbs/ft |
|
215°F |
190 |
180 |
170 |
160 |
150 |
140 |
130 |
120 |
| |
|
|
|
|
|
|
|
|
|
|
|
| RS2-16 |
15-7/8" |
1380 |
1083 |
960 |
863 |
758 |
654 |
540 |
461 |
371 |
9.8 |
| RS2-24 |
23-5/8" |
1920 |
1507 |
1320 |
1200 |
1054 |
910 |
780 |
641 |
516 |
13.4 |
| RS2-30 |
29-1/2" |
2280 |
1790 |
1620 |
1425 |
1252 |
1081 |
900 |
762 |
613 |
16.1 |
| RS2-36 |
35-5/8" |
2640 |
2072 |
1860 |
1650 |
1450 |
1251 |
1080 |
882 |
710 |
18.8 |
| RS2-78 |
78-3/4" |
6300 |
4946 |
4380 |
3938 |
3459 |
2989 |
25220 |
2104 |
1695 |
38.6 |
| RS2-84 |
84-5/8" |
6780 |
5322 |
4740 |
4238 |
3722 |
3214 |
2700 |
2265 |
1824 |
40.5 |
NOTE: Heat Outputs for
various AWT's include 15% Heat Effect for placement along
outside walls. Use the 215° F Output Rating with the
Correction Factor for more specific design conditions.
|